Honeywell

Honeywell CC-TDOD51 Experion Series C Non-Redundant Digital Output IOTA

SKU CC-TDOD51

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Honeywell

  • Product No.: CC-TDOD51

  • Country of origin:United States

  • Product Type: Digital Output Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 450g

  • Dimensions: 228 x 120 x 45 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The Honeywell CC-TDOD51 is a non-redundant Digital Output Input Output Termination Assembly (IOTA) designed for the Experion Series C platform. It serves as the physical field termination interface for the CC-PDOD51 24VDC sink-type digital output module, allowing process control signals to interface directly with actuators, solenoid valves, and interposing relays.

Operating within the Honeywell C300 controller architecture, the CC-TDOD51 provides streamlined signal distribution and terminal connection points without requiring external marshalling. Field wiring attaches directly to the two-level detachable terminal block, which accepts wiring up to 12 AWG (2.5 mm squared).

The assembly features conformal coating to withstand harsh industrial environments and incorporates electronic overcurrent protection. By distributing power across the bused backplane and housing the CC-PDOD51 output module, the assembly delivers reliable control switching for discrete automation circuits.

Features

  • Dedicated Sink Architecture: Specifically engineered for 32-channel 24VDC open-drain (sink) digital output operations.
  • Compact Footprint: Compact 9-inch (228 mm) non-redundant form factor optimizes enclosure space.
  • Conformal Coating: Standard board protection against moisture, dust, and aggressive industrial environments.
  • Detachable Terminations: Two-level detachable screw terminal blocks simplify initial installation, testing, and field maintenance.
  • Integrated Power Distribution: Receives 24VDC power directly through the bused IOTA carrier, eliminating extra field power wiring.
  • Galvanic Isolation: Offers 1000 VAC RMS system-to-field isolation when utilizing an external field power supply.

Applications

  • Solenoid Valve Control: Direct switching of 24VDC process solenoids and pneumatic actuators in process plants.
  • Interposing Relay Driving: Interfacing low-current digital outputs to higher-power control circuits and motor starters.
  • Discrete Alarm Indication: Controlling panel-mounted status lamps, annunciators, and field beacons.
  • General Process Automation: Integrated discrete output switching for chemical, oil and gas, power generation, and manufacturing facilities.

Technical Specifications

Parameter Specification
Manufacturer Honeywell
Model CC-TDOD51
System Platform Experion Series C
Compatible Module CC-PDOD51
Redundancy Non-Redundant
Number of Channels 32
Output Type Sink (Open Drain)
Operating Voltage Range 15 VDC to 30 VDC
Maximum Load Current 0.1 A per channel
Galvanic Isolation 1000 VAC RMS (System-to-Field)
On-State Voltage Drop 0 VDC typical (at 0.1 A max load)
Off-State Voltage 24 VDC typical
Maximum Off-State Leakage Current 100 µA
Maximum Switching Time 10 ms (Turn-On / Turn-Off)
Board Width / Size 9 inches (228 mm)
Terminal Wiring Capacity Up to 12 AWG (2.5 mm sq) stranded wire
Environmental Protection Conformally Coated

Connections / Interfaces

Terminal / Interface Function
IOM Mounting Slot Direct plug-in interface for CC-PDOD51 Digital Output Module
Field Wiring Terminals Two-level detachable screw terminals for 32 output channels
Power Bus Connections Screwed mechanical/electrical connection to the 24VDC bused carrier
Return / Ground Common Shared field return (ground) reference for sink-configured output loops

Installation Guidelines

  1. Safety Precaution: Disconnect system power before mounting or wiring the IOTA assembly to prevent electrical shock or hardware damage.
  2. Carrier Mounting: Secure the CC-TDOD51 onto the cabinet channel/carrier, ensuring firm contact with the 24VDC bus power distribution screws.
  3. Field Wiring: Land field output lines onto the two-level detachable terminal block using wire sizes up to 12 AWG (2.5 mm squared). Confirm output polarity matches the sink configuration.
  4. Module Insertion: Carefully align and plug the CC-PDOD51 Digital Output Module into the designated IOTA slot until fully seated.
  5. Pre-Power Verification: Verify wiring tightness, ensure proper grounding, and confirm field load currents do not exceed 0.1 A per channel.

Configuration / Commissioning / Replacement

  • Channel Fail-Safe Setup: Configure the FAILOPT parameter (Hold Last Value or Shed to Safe Value) via Experion Control Builder software.
  • Output Mode Selection: Program channels for latched, pulsed, or pulse-width modulated (PWM) operation based on application needs.
  • Hot-Swapping Module: The CC-PDOD51 IOM can be removed or replaced on the CC-TDOD51 IOTA without disturbing the field wiring.
  • Commissioning Verification: Exercise output channels through software override tools to verify field device state transitions and switching times under 10 ms.

FAQ

What is the primary function of the Honeywell CC-TDOD51?

The Honeywell CC-TDOD51 is a non-redundant Input Output Termination Assembly (IOTA) designed for the Experion Series C system. It holds the CC-PDOD51 digital output module and provides the physical screw terminals to connect up to 32 24VDC sink-type field devices.

Which digital output module is compatible with the CC-TDOD51 IOTA?

The CC-TDOD51 IOTA is specifically designed to support the Honeywell CC-PDOD51 24VDC sink-type digital output module. The module plugs directly into the assembly without requiring external wiring jumpers.

What size is the CC-TDOD51 assembly and does it support redundancy?

The CC-TDOD51 has a nominal width of 9 inches (228 mm) and is designed for non-redundant system configurations. For redundant applications, the 12-inch CC-TDOD61 IOTA must be used instead.

What are the output electrical limits for channels connected through this assembly?

Outputs connected through the CC-TDOD51 operate across a 15 to 30 VDC load range and support up to 0.1 A maximum load current per channel, featuring open-drain sink switching characteristics.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell CC-TDOD51 Experion Series C Non-Redundant Digital Output IOTA

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 3
Only 4 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Greyish White
Country of origin
United States
Power source
DC Power

Technical knowledge

Selecting Line Reactors and Output Filters for VFDs

Learn how line reactors, harmonic filters, output reactors, dV/dt filters, and sine filters address different VFD power-quality and motor-cable problems—and how to select them safely.

Light-On and Dark-On Photoelectric Sensor Logic

Learn how light-on and dark-on photoelectric sensor modes interact with through-beam, retroreflective, and diffuse sensing, PNP/NPN wiring, PLC logic, commissioning, and fault detection.

Designing H-Bridge Motor Drives Without Shoot-Through

A practical guide to H-bridge motor drives covering switching states, dead time, inductive current paths, PWM choices, protection, PCB layout, PLC interfacing, and staged commissioning tests.

Designing Mitsubishi FX PLC Sequences with STL and RET

Learn how Mitsubishi FX PLC STL and RET instructions structure conveyor and pneumatic sequences, with practical state design, transition logic, timeouts, diagnostics, and safe restart boundaries.

Selecting and Troubleshooting DIN Valve Connectors

A practical guide to selecting, wiring and diagnosing DIN-style valve connectors, including form identification, coil voltage, suppression, polarity, sealing, release-time effects and commissioning...

PLC or Microcontroller for Arc-Welding Motion Control?

A PLC and a microcontroller can both generate step-and-direction motion, but arc welding exposes major differences in EMC, I/O protection, diagnostics, maintainability, safety integration, and...