HIMA

HIMA H41q/H51q B9361 / B 9361 Assembly Kit

SKU B9361

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: HIMA

  • Product No.: B9361

  • Country of origin:Germany

  • Product Type: Assembly Kit

  • Payment: T/T, Western Union

  • Weight: 8500g

  • Dimensions: 222 mm x 248 mm x 483 mm (H x W x D)

  • Shipping port: Xiamen

  • Warranty: 12 months

The HIMA B 9361 is an assembly kit providing an additional 5 V power supply (loadable up to 18 A) for HIMA H51q safety systems. The B 9361 is utilized when the built-in power supply modules within the central rack are insufficient to supply the 5 V circuits (for example, when current requirement I > 18 A for three power supply modules F 7126 in a redundant control setup). Built around a 19-inch K 1408 central rack (5 units high) with an integrated cable tray, the B 9361 includes an F 7126 power supply module (24 V / 5 V, 10 A), an F 7131 power supply monitoring module, and rear-mounted decoupling, fusing, and fan monitoring units (Z 6011, Z 6012, and Z 6013). High availability is ensured as two out of three power supply modules can maintain the 5 V supply.

Features

  • Built around a 19-inch K 1408 central rack (5 units high, 5U) with integrated cable tray
  • Provides an additional 5 V power supply loadable up to 18 A for H51q systems
  • Equipped with 1 x F 7126 power supply module (24 V / 5 V DC, 10 A) in base kit
  • Option to expand with up to 2 x additional F 7126 power supply modules (PS2, PS3) operating with 5 V outputs in parallel
  • Equipped with 1 x F 7131 power supply monitoring module
  • Includes 14 socket connectors for installing standard F-type modules of the HIMA Planar System
  • Rear-mounted Z 6011 modules for decoupling and fusing to feed power supply modules
  • Rear-mounted Z 6012 fan module featuring fan run monitoring and fuse monitoring
  • Rear-mounted Z 6013 modules for decoupling and fusing of supply voltage for Z 6012
  • Redundant supply availability where 2 out of 3 power supply modules guarantee the 5 V supply

Applications

  • Additional 5 V DC power expansion for HIMA H51q safety control systems
  • Integration and housing of HIMA Planar System F-type modules
  • Power distribution and monitoring in industrial safety instrumentation installations

Ordering Information

Component Description Part / Module Designation
Central Rack 19-inch rack, 5 units high, with integrated cable tray 1 x K 1408
Rear Module Decoupling and fusing to feed power supply modules 3 x Z 6011
Rear Module Fan with fan run monitoring and fuse monitoring 1 x Z 6012
Rear Module Decoupling and fusing of supply voltage for Z 6012 2 x Z 6013
Included Module Power supply module 24 V / 5 V, 10 A (PS1) 1 x F 7126
Included Module Power supply monitoring module 1 x F 7131
Included Connectors Socket connectors for standard (F type) modules of HIMA Planar System 14 x Socket connectors
Optional Module Power supply module 24 V / 5 V (PS2, PS3) 2 x F 7126 (Separate order)
Optional Modules Standard (F type) modules of the HIMA Planar System 1...14 x F type modules (Separate order)

Technical Specifications

Parameter Specification
Manufacturer HIMA
Model B 9361
System Compatibility HIMA H51q Systems, HIMA Planar System
Rack Dimensions / Form Factor K 1408 central rack, 19 inches, 5 units high (5U)
Additional 5 V Capacity Loadable up to 18 A
Base Power Supply Module 1 x F 7126 (24 V / 5 V DC, 10 A)
Power Supply Redundancy 2 of 3 F 7126 modules guarantee 5 V supply
Internal Fuse Z 6011 4 A slow blow (5 x 20 mm, HIMA part no. 57 0174409)
Internal Fuse Z 6013 1.6 A slow blow (5 x 20 mm, HIMA part no. 57 0174169)

Connections/Interfaces

Connection Point Wire and Connection Details Fusing Function / Use
XG.21/22/23:2 (L+) RD 2.5 mm2, Faston 6.3 x 0.8 max. 16 A gL 24 VDC Supply for PS1...PS3
XG.21/22/23:1 (L-) BK 2.5 mm2, Faston 6.3 x 0.8 - Reference pole for 24 VDC Supply
XG.2: +5 V YE 2 x 2.5 mm2, Faston 6.3 x 0.8 (cross section 6 mm2 for distances > 2 m) - Output +5 VDC (Supply I/O subrack B 9302)
XG.3: GND GN 2 x 2.5 mm2, Faston 6.3 x 0.8 (cross section 6 mm2 for distances > 2 m) - Output GND (Supply I/O subrack B 9302, to be connected with GND of central rack)
XG.24:2 (L+) RD 1.5 mm2, Faston 6.3 x 0.8 - Output 24 VDC (Supply fuse monitoring and IO-CON in I/O subrack)
XG.25:2 (L+) RD 1.5 mm2, Faston 6.3 x 0.8 - Output 24 VDC (Supply fuse monitoring and IO-CON in I/O subrack for 2nd I/O bus B 5222-2, B 5223-2, B 5232-2, and B 5233-2 only)
XG.26:4/5/6 GY 0.5 mm2, Faston 2.8 x 0.8 max. 4 A slow blow Floating NO/NC contact for signalling (fuse and fan monitoring)
XG .4 - - Wiring ex works: Feeding L+ (24 V) for power supply module F 7126
XG .5 - - Wiring ex works: Feeding L- (24 V) for power supply module F 7126
XG .26: 2, 3 - - Wiring ex works: Power supply for fans
XG .26: 1 - - Wiring ex works: Wire for fuse monitoring
XG .1:9-11 - - Wiring by customer: Connections for monitoring of power supplies by F 7131
XG .21, XG .22, XG .23 - - Wiring by customer: Connections for Z 6011 (decoupling and fusing to feed power supply modules)
XG .24, XG .25 - - Wiring by customer: Connections for Z 6013 (decoupling and fusing of supply voltage for Z 6012 and feeding of coupling module F 7553 in I/O subrack)

Installation Guidelines

  • Earthing: Installation of the assembly kit requires a conductive connection to the frame or a separate earth connection installed according to EMC requirements. Connection PE earth uses Faston 6.3 x 0.8 mm. Pay strict attention to manufacturer recommendations when detaching and replugging Faston connectors.
  • 5 V Circuit Connection: The 5 V circuits of power supply modules in the central rack and in the additional power supply should not be switched in parallel; however, the GND of both power supplies must be connected together.
  • 5 V Output Wiring: For distances greater than 2 m between the 5 VDC output (XG.2 / XG.3) and the I/O subrack (B 9302), use a wire cross section of 6 mm2 instead of 2.5 mm2.

Compliance and Certifications

  • CE

FAQ

What is the HIMA B 9361 used for?

The HIMA B 9361 is an assembly kit used to provide an additional 5 V DC power supply loadable up to 18 A for HIMA H51q safety systems when central rack power is insufficient.

Which system does the module belong to?

The assembly kit belongs to HIMA H51q safety systems and accommodates standard F-type modules of the HIMA Planar System.

What modules are included in the standard B 9361 kit?

The kit includes a K 1408 central rack (5U, 19-inch), 1 x F 7126 power supply module (24 V / 5 V, 10 A), 1 x F 7131 power supply monitoring module, 14 slot connectors for F-type modules, and rear-mounted Z 6011, Z 6012, and Z 6013 modules.

How is power redundancy maintained in the B 9361?

Power availability is maintained because 2 out of 3 F 7126 power supply modules are capable of guaranteeing the 5 V supply.

How should the 5 V circuits be grounded and wired?

The 5 V circuits of the central rack and additional power supply must not be switched in parallel, but the GND of both power supplies must be connected together.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 5 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Technical knowledge

Selecting Line Reactors and Output Filters for VFDs

Learn how line reactors, harmonic filters, output reactors, dV/dt filters, and sine filters address different VFD power-quality and motor-cable problems—and how to select them safely.

Light-On and Dark-On Photoelectric Sensor Logic

Learn how light-on and dark-on photoelectric sensor modes interact with through-beam, retroreflective, and diffuse sensing, PNP/NPN wiring, PLC logic, commissioning, and fault detection.

Designing H-Bridge Motor Drives Without Shoot-Through

A practical guide to H-bridge motor drives covering switching states, dead time, inductive current paths, PWM choices, protection, PCB layout, PLC interfacing, and staged commissioning tests.

Designing Mitsubishi FX PLC Sequences with STL and RET

Learn how Mitsubishi FX PLC STL and RET instructions structure conveyor and pneumatic sequences, with practical state design, transition logic, timeouts, diagnostics, and safe restart boundaries.

Selecting and Troubleshooting DIN Valve Connectors

A practical guide to selecting, wiring and diagnosing DIN-style valve connectors, including form identification, coil voltage, suppression, polarity, sealing, release-time effects and commissioning...

PLC or Microcontroller for Arc-Welding Motion Control?

A PLC and a microcontroller can both generate step-and-direction motion, but arc welding exposes major differences in EMC, I/O protection, diagnostics, maintainability, safety integration, and...